Instruction References
Processing
• Stores the IPv4 setting parameter of S in the operation work area, and initializes the
Ethernet unit.
• Communication is not available during initialization.
• The unit configuration data of Ethernet never be rewritten. Executing this instructioni
initializes the Ethernet unit with a value specified in the operation work area. For the items
that has not been changed with the instruction, the values specified in the unit configuration
are applied.
• The statuses such as the establishment of IPv4 address or cable disconnection can be
confirmed in the input relay area WX6 (X61 to X69).
WX6
Bit0: Cable disconnected / Cable conducted
Bit1: Ethernet being initialized / Ethernet initialization completed
Bit2: IP address established / IP address not established
Bit4: FTP server preparation completed / FTP server preparation not completed
Bit5: FTP client preparation completed / FTP client preparation not completed
Bit6: Reserved
Bit7: Reserved
Bit8: HTTP client preparation completed / HTTP client preparation not completed
Bit9: Mail send preparation completed / Mail send preparation not completed
• When a specified IP address is outside of the addressable range, an error is set to CY flag
and it becomes no operation.
• It is executable when the Ethernet initialization active (X61) is OFF. If it is ON when
executing the instruction, an error is set to CY flag and it becomes no operation.
Setting result
• The result of the above settings can be confirmed in the system relay (SR9) and system data
(SD29).
SR9 (CY flag)
0: Normal
1: Error
7-4
SD29
0: Normal
1: IPv4 address, 2: Subnet mask, 3: Default gateway, 4: Combination,
11: Ethernet initialization active