 Control relay
Name
Transfer request relay
Transfer active relay
Retry active relay
Execution done relay
Execution result relay
Transfer direction relay
Reserved for system
Transfer cancel request
relay
Transfer disable relay
(Note): The state of control relays can be read with ETSTAT instruction.
 Completion code
Name
Execution done code
Transfer done code
(Note): The state of completion codes can be read with ETSTAT instruction.
 FTP client preparation done (WX6 bit 5)
Name
FTP client preparation
done (X65)
 Flag operation
Name
Latest error (SR7)
Hold error (SR8)
CY flag (SR9)
(Note): For information of the error codes stored in the system data SD29, refer to 8.1.1 List of SD29 Detail Codes.
Bit No.
Description
0
0: No request, 1: Request
1
0: Stop, 1: During transfer
2
0: No retry, 1: During retry
3
0: During process, 1: Instruction execution complete
4
0: Normal 1: Failed
5
0: Send, 1: Receive
6 to 13
-
14
0: Not cancel, 1: Cancel
15
0: Transfer enabled, 1: Transfer disabled
No. of
Description
words
1
Execution completion code
1
Response code of FTP client
Bit No.
Description
0: FTP client preparation incomplete, 1: FTP client preparation
5
complete
Description
Set when the slot number specified with UNITSEL is not [S1]=100 (built-in ET-LAN).
To be set in case of out-of-range in indirect access (index modiication).
Set when the FTP client prepartion done (X65) is OFF at the time of the execution
of instruction.
Set when an out-of-range value is specified for parameters.
Set when the transfer request relay of a specified ID is "Request".
Set when executed in an interrupt program.
Set when a file transfer that has not been specified with the transfer setting
instruction or the tool software is specified.
Set when executed while the Ethernet cable is disconnected. The detail code set in
SD29 is "10: Ethernet cable disconnected".
Set when executed during the initialization of Ethernet. The detail code set in SD29
is "11: Ethernet initialization active".
4.4 How to Use File Transfer
4-41

Advertisement

Table of Contents
loading