8 PARAMETERS SETTING

Start the controller, then press
below:
1 Set Parameters
Fig1
2 Information
3 Language
4 Mode Select
 Parameters Setting
When entering password interface, inputting "1234" can set part of the parameter
while "0318" can set all the items. If there is need to set more
items in
Table 1
parameters, please contact the factory.
NOTES:
1. For HGM410E, there are no items from 1 to 5 in
about mains in auxiliary output 1-5.
2. Please change the controller parameters when generator is in standby mode only
(e. g. Crank disconnect conditions selection, digital input, digital output, various
delay), otherwise, shutdown and other abnormal conditions may occurs.
3. Over voltage set value must be higher than under voltage set value, otherwise over
voltage and under voltage condition may occur simultaneously.
4. Over speed set value must be higher than under speed set value, otherwise over
speed and under speed condition may occur simultaneously.
5. Please set the generator frequency value as low as possible when cranking, in
order to make the starter be separated quickly as soon as possible.
6. Digital input 1~4 could not be set as same items; otherwise, there are abnormal
functions. However, the digital output 1~5 can be set as same items.
7. If need to shut down after cooling, please set any digital input as "High
Temperature Stop Input", then connect this input port to GND.
 Information
LCD will display software version, issue date of the controller.
Note: In this interface, press
HGM400E Series Genset Controller
HGM400E Series Automatic Control Module
to enter into the parameters setting menu, see fig 1
will display the digital inputs and outputs status.
ISSUE 2013-08-28
Table
1; there are no digital outputs
Version 1.1
Page 33 of 41