Smartgen HGM410E User Manual page 21

Hgm400e series genset controller
Table of Contents

Advertisement

No
Items
12
Safety On Delay
13
Start Idle Time
14
Warming Up Time
15
Cooling Time
16
Stop Idle
ETS
Solenoid
17
Hold
18
Fail to Stop Delay
19
Close Time
20
Flywheel Teeth
Gen
Abnormal
21
Delay
22
Gen Over Voltage
HGM400E Series Genset Controller
HGM400E Series Automatic Control Module
Range
(1-60)s
(0-3600)s
(0-3600)s
(3-3600)s
(0-3600)s
(0-120)s
(0-120)s
(0-10)s
(10-300)
(0-20.0)s
(30-620)V
ISSUE 2013-08-28
Default
Alarms for low oil pressure, high
temperature, under speed, under
10
frequency/voltage,
failure are inactive.
Idle running time of genset when
0
starting.
Warming time between genset
10
switch
on
running.
Radiating time before genset
10
stop, after it unloads.
Idle running time when genset
0
stop.
Stop electromagnet's power on
20
time when genset is stopping.
Time between ending of genset
idle delay and stopped when
"ETS time" is set as 0;
0
Time between ending of ETS
hold delay and stopped when
"ETS time" is not 0.
Pulse width of mains/generator
5.0
switch on. When it is 0, means
output constantly.
Tooth number of the engine, for
judging
118
disconnect
inspecting of engine speed. See
the installation instructions.
The alarm delay of generator
10.0
over voltage and under voltage.
When generator voltage has
exceed the set value and the
"Gen
abnormal
264
expired, Gen Over Voltage is
active. When set the value as
620V, the controller does not
detect over voltage signal.
Version 1.1
Description
charge
and
high
speed
of
starter
crank
conditions
delay"
Page 22 of 41