Smartgen HGM410E User Manual page 22

Hgm400e series genset controller
Table of Contents

Advertisement

No
Items
Generator Under
23
Voltage
24
Under Speed
25
Over Speed
26
Under Frequency
27
Over Frequency
28
High Temperature
HGM400E Series Genset Controller
HGM400E Series Automatic Control Module
Range
(30-620)V
(0-6000)RPM 1200
(0-6000)RPM 1710
(0-75.0)Hz
(0-75.0)Hz
(80-140)º C
ISSUE 2013-08-28
Default
When generator voltage has
fallen below the set value and the
"Gen
abnormal
196
expired, Gen Under Voltage is
active. When set the value as
30V, the controller does not
detect under voltage signal.
When engine speed has fallen
below the set value for 10s,
Under Speed is active. It will
initiate a shutdown alarm signal.
When engine speed has exceed
the set value for 2s, Over Speed
is
active.
shutdown alarm signal.
When generator frequency has
fallen below the set value but Not
45.0
equal to 0 for 10s, Under
Frequency is active. It will initiate
a shutdown alarm signal.
When generator frequency has
exceed the set value for 2s, Over
57.0
Frequency is active. It will initiate
a shutdown alarm signal.
When the temperature value of
the external temperature sensor
exceeds the set value, high
temperature
Detecting only after safety on
98
delay is over. If the set value is
140, high temperature signal will
not be sent (this only concerns
external temperature sensor, not
high
temperature
config. input port).