3) Once this "stop delay" has expired, the Generator Breaker will open and the "Cooling
Delay" is then initiated. After "Transfer Delay", the mains close relay will be
energized; mains will take load; generator power indicator will extinguish while mains
power indicator will illuminate.
4) During "Stop Idle" Delay (if configured), idle relay is energized.
5) "ETS Solenoid Hold" begins, ETS relay is energized while fuel relay is de-energized.
6) "Fail to Stop Delay" begins, complete stop is detected automatically.
7) Generator is placed into its standby mode after its complete stop. Otherwise, fail to
stop alarm is initiated and the corresponding alarm information is displayed on LCD.

4.4 MANUAL START/STOP OPERATION

1) HGM420E: Manual mode is selected by pressing the
button will illuminate to confirm the operation; Press
then choose "Test Mode". Under the two modes, press
it can automatically judge crank success and accelerate to high speed running. If high
temperature, low oil pressure, over speed and abnormal voltage occur during genset
running, controller can effectively protect genset to stop (detail procedures please
refer to No.4~9 of Auto start sequence). Under Manual Mode
load breaker won't transfer; if mains abnormal, load breaker will transfer to generator.
Under Test Mode, after genset high speed normal running, no matter mains normal
or not, load will be transferred to generator.
2) HGM410E: Manual mode is selected by pressing the
button will illuminate to confirm the operation; Then press
generator, it can automatically judge crank success and accelerate to high speed
running. If high temperature, low oil pressure, over speed and abnormal voltage
occur during genset running, controller can effectively protect genset to stop (detail
procedures please refer to No.4~9 of Auto start sequence). After genset high speed
normal running, controller will send Gen Closed signal.
3) Manual stop: pressing
please refer to No.3~7 of Auto stop sequence)
HGM400E Series Genset Controller
HGM400E Series Automatic Control Module
key can shut down the running genset. (detail procedures
ISSUE 2013-08-28
button; a LED besides the
key, select "Mode Select",
button to start the genset,
, if mains normal,
button; a LED besides the
button to start the
Version 1.1
Page 12 of 41

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hgm420e

Table of Contents