Connections - Smartgen HGM410E User Manual

Hgm400e series genset controller
Table of Contents

Advertisement

6

CONNECTIONS

Compared with HGM420E, HGM410E has no Mains AC Voltage input terminals. The
rear panel of HGM410E and HGM420E is as below.
Description of terminal connections:
Pin
Function
1
B-
2
B+
3
Aux. Output 1
4
Crank
5
Aux. Output 2
6
Aux. Output 3
7
Aux. Input 1
8
Aux. Input 2
9
Aux. Input 3
HGM400E Series Genset Controller
HGM400E Series Automatic Control Module
Cable
Size
2
1.5mm
2
1.5mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
ISSUE 2013-08-28
Description
DC
power
supply.
negative of starter battery.
DC
power
supply.
positive of starter battery. If wire length is
over 30m, better to double wires in
parallel. Max. 20A fuse is recommended.
B+ is supplied by 2 point, rated 5A.
B+ is supplied by 2 point, rated 5A.
Connect to starter coil.
B+ is supplied by 2 point, rated 5A.
B+ is supplied by 2 point, rated 5A.
Ground
connected
active (B-)
Ground connected is
active (B-)
Ground
connected
active (B-); Can be used
Version 1.1
Connected
with
Connected
with
is
See
Table 3
is
Page 18 of 41

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hgm420e

Table of Contents