(Table 3) - Smartgen HGM410E User Manual

Hgm400e series genset controller
Table of Contents

Advertisement

7.3 PROGRAMMABLE
CONNECT GND (B-) (TABLE 3)
No
Items
0
Not Used
High
Temperature
1
Input
Low
Oil
2
Warning Input
3
Auxiliary Warning
Emergency
4
Shutdown
High
Temperature
5
Stop Input
6
Generator Closed
7
Mains Closed
Inhibit
8
Temperature Stop
Inhibit
Low
9
Pressure Stop
10
Remote Start
11
Fuel Level Warn
12
Coolant Level Warn
Fuel
13
Shutdown
Coolant
14
Shutdown
15
Auto Start Inhibit
HGM400E Series Genset Controller
HGM400E Series Automatic Control Module
INPUT
If these signals are active after safety on delay,
shutdown alarm will be immediately initiated.
Pressure
Only warning and not stops if this input is active.
Shutdown alarm will be immediately initiated if this
input is active.
When the gen-set is running normally and this signal is
activated, if there is a high temperature situation, the
controller will first cool down the generator and then
stop it; if the signal is deactivated and a high
temperature situation occurs, the controller will shut
down the gen-set without cooling down.
HGM410E without
High
When it is active, prohibit stopping when high
temperature occurs. Note 1
Oil
When it is active, prohibit stopping when low oil
pressure occurs. Note 2
HGM420E without
Level
Level
In Auto mode, if this input is active, whether mains is
normal or not (HGM420E) or a remote start signal
occurs (HGM410E), the controller will not give a start
command to the generator. If generator is normal
running, stop command won't be executed. When this
input is deactivated, genset will automatically start or
stop according to the mains status (normal or
abnormal).
ISSUE 2013-08-28
1-4
TABLE
Description
Version 1.1
(ACTIVE
WHEN
Page 30 of 41