Smartgen HGM410E User Manual page 24

Hgm400e series genset controller
Table of Contents

Advertisement

No
Items
36
Current Trans.
Full
Current
37
Rating
Over
Current
38
Percentage
Over
Current
39
Delay
40
Fuel Pump On
41
Fuel Pump Off
42
Digital Output 1
43
Digital Output 2
44
Digital Output 3
45
Digital Output 4
46
Digital Output 5
47
Digital Input 1
Digital
Input
48
Active
Digital
Input
49
Delay
50
Digital Input 2
Digital
Input
51
Active
Digital
Input
52
Delay
53
Digital Input 3
Digital
Input
54
Active
Digital
Input
55
Delay
HGM400E Series Genset Controller
HGM400E Series Automatic Control Module
Range
(5-6000)/5
(5-6000)A
(50-130)%
(0-3600)s
(0-100)%
(0-100)%
(0-17)
(0-17)
(0-17)
(0-17)
(0-17)
(0-15)
1
(0-1)
1
(0-20.0)s
(0-15)
2
(0-1)
2
(0-20.0)s
(0-15)
3
(0-1)
3
(0-20.0)s
ISSUE 2013-08-28
Default
500
The ratio of external CT
Generator's
500
standard of load current.
When the load current
exceed the set value, "over
120
current" delay is initiated.
When load current has exceed
the set value and the "over
current" delay has expired, over
1296
current is initiated. When the set
value is 0, only warning and not
to shutdown the generator.
When fuel level has fallen below
the set value for 10s, "Fuel Pump
25
On" alarm is initiated.
When fuel level has exceed the
set value for 10s, "Fuel Pump
80
Off" alarm is initiated.
Factory
14
Output
Factory default: Energized To
2
Stop
3
Factory default: Idle Control
5
Factory default: Close Generator
6
Factory default: Mains Closed
Factory
1
Temperature Input
0
Factory default: Close to active
2.0
Factory default: Low Oil Pressure
2
Warning Input
0
Factory default: Close to active
2.0
10
Factory default: Remote Start
0
Factory default: Close to active
2.0
Version 1.1
Description
rated
current,
default:
Fuel
Relay
default:
High
Page 25 of 41