Protection; Warnings - Smartgen HGM410E User Manual

Hgm400e series genset controller
Table of Contents

Advertisement

5 PROTECTION

5.1 WARNINGS

When controller detects the warning signal, only alarm and not lead to shutdown. The
alarm information will be displayed on LCD.
Warnings types are as follows,
No.
Items
High
1
Temperature
Low
2
Pressure
Gen
Over
3
Current
4
Fail To Stop
5
Low Fuel Level
Charge
6
Failure
Battery Under
7
Volt
Battery Over
8
Volt
HGM400E Series Genset Controller
HGM400E Series Automatic Control Module
When the controller detects that engine temperature has
exceeded the pre-set value while shutdown is prohibited, or
detects that the Aux. input high temperature while shutdown
is prohibited, it will initiate a warning alarm and the
corresponding alarm information will be displayed on LCD.
When the controller detects that the oil pressure has fallen
below the pre-set value while shutdown is prohibited, or
Oil
detects that the Aux. input low oil pressure while shutdown is
prohibited, it will initiate a warning alarm and the
corresponding alarm information will be displayed on LCD.
When the controller detects that the genset current has
exceeded the pre-set value and the over current delay has
expired, it will initiate a warning alarm and the corresponding
alarm information will be displayed on LCD.
After "fail to stop" delay/ ETS delay, if gen-set does not stop
completely, it will initiate a warning alarm and the
corresponding alarm information will be displayed on LCD.
When the controller detects that the fuel level has fallen
below the pre-set value while shutdown is prohibited, or
detects that the Aux. input low fuel level while shutdown is
prohibited, it will initiate a warning alarm and the
corresponding alarm information will be displayed on LCD.
When the controller detects that charger voltage has fallen
Alt
below the pre-set value, it will initiate a warning alarm and
the corresponding alarm information will be displayed on
LCD.
When the controller detects that battery voltage has fallen
below the pre-set value, it will initiate a warning alarm and
the corresponding alarm information will be displayed on
LCD.
When the controller detects that battery voltage has
exceeded the pre-set value, it will initiate a warning alarm
and the corresponding alarm information will be displayed on
LCD.
ISSUE 2013-08-28
Description
Version 1.1
Page 13 of 41