PLC Error Messages with COM 115F

Appendix B gives an overview of all error messages and indicates the possible causes of error.
Proceed as follows for the OVERALL RESET remedy:
Safety mode:
OVERALL RESET
Test mode:
- OVERALL RESET
- Load system
- STOP
- RUN
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
02
01
User times cannot be
updated:
PL or CPU error
Additional info. 1:
User time decrement
in A/10msec.
Additional info. 2:
User time decrement
in B/10msec.
02
02
Interval between 2 FB 254s
for updating time > con-
figured limit
Additional info. 1:
Unit time difference/10msec.
Additional info. 2:
Configured
limit value/10msec.
Additional info 3:
Localization parameter
EWA 4NEB 811 6149-02
Possible Cause
Error group No. 20
-
PL (Parallel link) defective
-
CPU defective
(in A or B)
Error group No. 14
Configured error:
Time difference between 2 synchr.
FB calls is too long
(Parameter: SYNC KM 0000001)
Uniform actual time interval
between 2 FB 254s in 10 msec.,
decimal display
Max. configured time interval
between 2 FB 254s in 10 msec.,
decimal display
FB 254 call intervals with the relevant
localization parameter too long
Hex display
PLC Error Messages
Remedy
- Replace PL
- Replace CPU
Warm restart:
1. POWER OFF/ON
2. Stop/Run
Select intervals between 2
synchr. calls max. configured
time difference
Warm restart:
1. Stop/Run
B-1