Blocks
COM 115F is used to configure the analog value representation of the module (channel type).
There are three methods of wire-break detection:
Hardware wire-break detection
This is implemented on the 460 AI module with the 498-1AA11 range card. The condition code
bit F is set in the event of a wire-break and evaluated by FB 250 ANEI.
Wire-break detection by FB 250 ANEI
The 460 AI module with range cards 498-1AA51 or 498-1AA71 and the 463 AI module with the
jumper setting for the range 4 to 20 mA, use the life-zero procedure for wire-break detection:
If the sensors, the signal path and the input module are intact, the smallest permissible value is
4 mA. All values less than 3 mA are interpreted by FB 250 ANEI as wire-break.
Wire-break detection by the user program and FB 250 ANEI
All measuring ranges of both AI modules which do not permit wire-break detection as in
and must use the following procedure supported by the user program.
For this purpose, a wire-break range in the standard value range must be set with the "ODGR"
and "UDGR" parameters of FB 250 ANEI.
The error bit "F" is set in FB 250 if
the analog value is within the "ODGR" and "UDGR" limits
and
the "DRAK" bit is set in the control program ( 6.9).
Testing the line for wire-break only makes sense with this procedure if the analog value is
outside the wire-break limits.
6-6
S5-115F Manual
EWA 4NEB 811 6149-02