Siemens SIMATIC S5 Manual page 271

Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

S5-115F Manual
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
23
01
Inconsistencies during test
read of SINEC L1 receive
buffer: CPU error
Additional info. 1:
Message source No.
23
02
Inconsistent definition of
Send mailbox: CPU error
Additional info. 1
Message destination No.
23
03
Receive mailbox could not be
overwritten:
CPU error
EWA 4NEB 811 6149-02
Possible Cause
Error group No. 01
-
CPU error
Error group No. 01
-
Falsification of Send mailbox
definition by CPU, HW or
operating system error
Error group No. 01
-
Falsification of Receive mailbox
definition by CPU, HW or
operating system error
PLC Error Messages
Remedy
-
Replace CPU
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
B-11