Siemens SIMATIC S5 Manual page 304

Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
53
01
PL access not possible:
PL, CPU HW or IM error
Additional info. 1:
Job No.
Additional info. 2:
Call location parameter
53
02
CPU error
Additional info. 1:
Logical operating system
program counter
Additional info. 2:
Call location parameter
Additional info. 3:
Job No.
53
03
Synchronization of A and B
not possible:
CPU HW or PL error
Additional info. 1:
Logical user program
counter A
Additional info. 2:
Logical user program
counter B
B-44
Possible Cause
Error group No. 01
Continuous READY on PL access,
recognized in job header:
-
PL HW error
-
CPU HW error
-
IM error
Error group No. 13
Job number not defined
-
CPU error
Error group No. 23
User LPLZ in A different to B
-
CPU error
-
PL error
S5-115F Manual
Remedy
-
Replace PL
-
Replace CPU
-
Replace IM
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Replace CPU
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
On first occurrence of the error:
OVERALL RESET
If the error has not been re-
moved after several OVERALL
RESETs:
-
Replace CPU
-
Replace PL
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
EWA 4NEB 811 6149-02

Advertisement

Table of Contents
loading

This manual is also suitable for:

S5-115f

Table of Contents