Siemens SIMATIC S5 Manual page 199

Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

Error Diagnostics
Table 5-9. Types of Error which Can Be Interpreted by COM 115F (Continued)
Value
Byte 0
16
Handling
17
Handling
18
Network interrupt
19
I/O modules
20
CPU, PL, PS
21
Scan time exceeded
22
Configuration
23
Error in other subunits
or CPU error
24
Handling
25
Battery fault
26
STS operation in user program (immediate stop)
29
Cannot be evaluated
30
Handling
31
Handling
*
Vol. 1, 4.1.4 of the Manual
5-18
Type of Error
S5-115F Manual
Response in
Safety Mode
*
Large stop loop
Large stop loop
Large stop loop
Large stop loop
Lesser stop loop
Lesser stop loop
Large stop loop
Partner response
Lesser stop loop
Lesser stop loop
Large stop loop
Large stop loop
Lesser stop loop
Lesser stop loop
Wait for programmer input
EWA 4NEB 811 6149-02