Siemens SIMATIC S5 Manual page 311

Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

S5-115F Manual
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
74
03
DB1 not present in PLC:
Handling error
74
04
PLC cannot be activated:
Handling error or CPU error
Additional info. 1:
I/O module type
Additional info. 2:
DB No.
Additional info. 3:
DB address
EWA 4NEB 811 6149-02
Possible Cause
Error group No. 16
-
DB1 not in user EPROM
(Safety mode)
-
DB1 not loaded in PLC
(Test mode)
Error group No. 16
-
Configuration DB missing
-
Configuration DB address
wrongly calculated by operating
system
PLC Error Messages
Remedy
-
Configure DB1 with
COM 115F and transfer to PLC
Warm restart:
1. Stop/Run
-
Check configuration DBs
-
Replace CPU
Warm restart:
1. Stop/Run
B-51