6.3

Loadable Function Blocks

Frequently repeated or particularly complex program sections (such as event signalling functions
and compute functions) are programmed in function blocks. These blocks have specifiable
parameters and an extended operation set (e.g. Jump operations within a block).
The loadable function blocks are subdivided into
User-written function blocks
Standard function blocks
User-Written Function Blocks
As is the case for all other blocks, function blocks written by the user must be examined by the
authorized inspector.
At the very least, such an examination comprises a verbal description of the function, functional
tests and a code analysis.
Standard Function Blocks
In the S5-115F, standard function blocks may be used only when they have been prototype-tested.
The standard FBs for the S5-115F implement the same functions as the standard FBs for the
SIMATIC S5 U-range controllers, but have been adapted to state-of-the-art failsafe technology. An
overview of the standard function blocks available for the S5-115F can be found in Catalog ST 57.
There are reaction-free and failsafe standard FBs. Only failsafe standard FBs may be used to form
signals relevant to the system's failsafety. When initializing the block parameters, note that
output parameters are failsafe only when all input parameters are failsafe.
All standard FBs are identified by a library number which, in conjunction with other measures,
protect the blocks against falsifications caused by transfer errors or disk errors.
Note the following when using loadable standard FBs:
In the safety mode, the operating system checks all standard FBs for integrity
Standard FBs for the SIMATIC S5 U-range controllers are not allowed, and are rejected in the
safety mode
The authorized inspector's examination of the standard FBs limits itself to
- a comparison of the library number with the one specified in the report
- checking for proper use of the standard FBs
- checking the FB calls for correctness and checking the parameter initialization routine for
the FBs as per the block description
- making sure that the provisions laid down in the report have been upheld
Note
When using standard FBs, flag words FW 200 to FW 254 may be used in the application
program only when these flags are saved prior to invoking a standard FB and reloaded
once that FB has executed.
EWA 4NEB 811 6149-02
Blocks
6-25