S5-115F Manual
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
30
13
Self-test in A and B not
synchronous: CPU error
Additional info. 1:
FXAE TEST ANZ in A
Additional info. 2:
FXAE TEST ANZ in B
EWA 4NEB 811 6149-02
Possible Cause
Error group No. 13
The FXAE TEST ANZ datum is not
identical in A and B.
-
CPU error (one-sided overwrite of
memory location)
PLC Error Messages
Remedy
-
Replace CPU
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
B-27