Siemens SIMATIC S5 Manual page 283

Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

S5-115F Manual
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
30
01
Self-test in A and B not
synchronous: CPU error
Additional info. 1:
FXTEKO in A
Additional info. 2:
FXTEKO in B
30
02
Self-test in A and B not
synchronous: CPU error
Additional info. 1:
FXTE ZEI0 H in A
Additional info. 2:
FXTE ZEI0 H in B
30
03
Self-test in A and B not
synchronous: CPU error
Additional info. 1:
FXTE ZEI0 L in A
Additional info. 2:
FXTE ZEI0 L in B
EWA 4NEB 811 6149-02
Possible Cause
Error group No. 13
Test components (FXTEKO) in A and B
not identical
-
CPU error
(one-sided overwrite of memory
location)
Error group No. 13
Test pointer 0 (FXTE ZEI0 H) is not
identical in A and B.
-
CPU error
(single-sided overwrite of me-
mory location)
Error group No. 13
Test pointer 0 (FXTE ZEI0 H) is not
identical in A and B.
-
CPU error
(one-sided overwrite of memory
location)
PLC Error Messages
Remedy
-
Replace CPU
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Replace CPU
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Replace CPU
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
B-23

Advertisement

Table of Contents
loading

This manual is also suitable for:

S5-115f

Table of Contents