PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
29
01
User operation sequence for
LPLZ incrementation is
missing: Program error
Additional info. 1:
Block type
Additional info. 2:
Block No.
Additional info. 3:
User memory initial address
29
02
Error during function test of
the SSP: CPU HW error
Additional info. 1:
Block type
Additional info. 2:
Block No.
Additional info. 3:
User memory initial address
B-22
Possible Cause
Error group No. 12
Operation sequence:
L
FWO
L
KF+1
+F
T
FWO
is missing
Type of block in which the LPLZ
incrementation is missing,
character display
Number of the block,
decimal display
Initial address of the block in the user
memory,
hex display
Error group No. 03
SAZ test has detected error in SSP:
-
CPU HW error
S5-115F Manual
Remedy
Insert operation sequence in the
relevant block
Warm restart:
1. Stop/Run
-
Replace CPU
Warm restart:
1. Stop/Run