PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
74
01
Configured I/Os not plugged
in or wrong IM306 slot
address
Additional info. 1:
Subunit
Additional info. 2:
I/O module type
Additional info. 3:
Smallest I/O word No.
74
02
Non-configured I/Os are
connected or DB1 is not
available in the user program
Additional info. 1:
Subunit
Additional info. 2:
I/O module type
Additional info. 3:
Smallest I/O word No.
B-50
Possible Cause
Error group No. 16
Handling error:
-
Module not plugged in
-
Module defective
-
Wrong address set in IM306
-
IM306 defective
Subunit in which the error was
discovered, character display
Relevant I/O module (DI, DQ, AI, AQ
module),
character display
Word address of the first erroneous
I/O module found,
decimal display
Error group No. 16
Handling error:
-
Wrong I/O module plugged in
-
Connected I/O modules not fully
configured;
-
DB1 not available
Subunit in which the error was
discovered, character display
Relevant I/O module,
character display
Word address of the first erroneous
I/O module found,
decimal display
S5-115F Manual
Remedy
-
Plug in module
-
(if necessary, change
configuration)
-
Replace module
-
Check addressing in IM306
-
Replace IM306
Warm restart:
1. Stop/Run
-
Check I/O modules
-
Check I/O configuration
-
Check DB1
Warm restart:
1. Stop/Run
EWA 4NEB 811 6149-02