PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
47
01
Error during test of processor
RAM:
CPU HW error
Additional info. 1:
Check byte address
Additional info. 2:
Setpoint contents check byte
Additional info. 3:
Actual contents check byte
47
02
Error during test of processor
RAM:
CPU HW error
Additional info. 1:
Environment byte address
Additional info. 2:
Check byte address
Additional info. 3:
Setpoint contents
environment byte
Additional info. 4:
Actual contents
environment byte
Additional info. 5:
Contents check byte
B-38
Possible Cause
Error group No. 02
Internal µP8032 RAM,
Error during read-after-write check
of test byte:
-
CPU HW error
Error group No. 02
Internal µP8032 RAM:
Error during read-after-write check
of environment byte
-
CPU HW error
S5-115F Manual
Remedy
-
Replace CPU
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Replace CPU
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
EWA 4NEB 811 6149-02