Siemens SIMATIC S5 Manual page 268

Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
17
04
Wire-break in safety-
related AI:
I/O error
e.g.
Additional info 1:
AI word No.
Additional info 2:
CH AQ word No.
Additional info 3:
CH DQ word No.
B-8
Possible Cause
Error group No. 09
I/O module single comparison error
Error group No. 08
I/O error burst
(only in the case of CPU 942-7UF13
with I/O ETV 3 or 4)
AI comparison error:
-
Cable to AI 463 module
interrupted in the case of channel
types 3 to 6
-
V
selected too high for AI 463
min
and channel types 5, 6
Decimal display
Check AQ word No.
only with subunit ID, decimal display
Check DQ word No.
only with subunit ID, decimal display
S5-115F Manual
Remedy
-
Check cables
-
Reconfigure V
min
Warm restart in the case of
individual error and signal group
No. 0 (Stop mode)
1. Stop/Run
Warm restart in the case of
individual error and signal group
No. 1 to 28
(passivation):
a) Test mode
1. Power OFF/ON
2. Stop/Run
b) Safety mode
1. OVERALL RESET
Warm restart in the case of error
burst:
1. POWER OFF/ON
2. Stop/Run
This does not cancel passivation.
To do so, see above: Warm
restart in the case of passivation.
EWA 4NEB 811 6149-02

Advertisement

Table of Contents
loading

This manual is also suitable for:

S5-115f