Siemens SIMATIC S5 Manual page 117

Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

S5-115F Manual
Extended pulse
Example:
Output Q 4.1 is set for a specific time when the signal at input I 3.1 changes to "1". The time is
indicated in IW 15.
Timing Diagram
Signal states
1
0
1
0
t
STL
A
I
3.1
L
IW
15
SE
T
2
NOP 0
*
NOP 0
*
NOP 0
*
A
T
2
=
Q
4.1
*
NOP 0 is required if the program is to be represented in LAD or CSF in the PG 635, PG 670, PG 675, PG 685, PG 695 or
PG 750 programmers. NOP 0 operations are automatically assigned when programming in LAD and CSF.
EWA 4NEB 811 6149-02
I 3.1
Q 4.1
Time
t
CSF
T 2
1
EXT
I 3.1
IW 15
TV
BI
DE
R
Q
Q 4.1
STEP 5 Operations
Circuit Diagram
I 3.1
T 2
T 2: Time relay with pulse
generation
LAD
T 2
I 3.1
1
EXT
TV
BI
IW 15
DE
R
Q
Q 4.1
Q4.1
3-21

Advertisement

Table of Contents
loading

This manual is also suitable for:

S5-115f

Table of Contents