PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
33
01
QVZ during reading of AI
module:
I/O module error
Additional info. 1:
AI word No.
33
02
QVZ during output of CH
relay DQ:
I/O module error
Additional info. 1:
CH relay DQ word No.
33
03
QVZ during output of CH AQ:
I/O module error
Additional info. 1:
CH AQ word No.
B-34
Possible Cause
Error group No. 19
-
AI module not available
-
AI module defective
-
IM306 defective
-
AI module with IM306 wrongly
addressed
Address of the AI channel which
contained QVZ,
decimal display
Error group No. 19
-
Module not available
-
Module defective
-
IM306 defective
-
Module with IM306 wrongly
addressed
Address of CH relay DQ module
which contained QVZ,
decimal display
Error group No. 19
-
Module not available
-
Module defective
-
IM306 defective
-
Module with IM306 wrongly
addressed
Address of the CH AQ channel which
contained the QVZ,
decimal display
S5-115F Manual
Remedy
- Plug in module
(if necessary, change
configuration)
- Replace module
- Replace IM306
- Check addressing
Warm restart:
1. Stop/Run
-
Plug in module
(if necessary, change
configuration)
- Replace module
- Replace IM306
- Check addressing
Warm restart:
1. Stop/Run
-
Plug in module
(if necessary, change
configuration)
- Replace module
- Replace IM306
- Check addressing
Warm restart:
1. Stop/Run