Siemens SIMATIC S5 Manual page 292

Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
32
05
Error during DI module test
in A
Additional info. 1:
DI byte No.
Additional info. 2:
CH DQ No.
Additional info. 3:
Bit No.
B-32
Possible Cause
Error group No. 10
I/O module test individual error
Error group No. 08
I/O error burst
(only in the case CPU 942-7UF13 with
I/O ETV 3 or 4)
DI module test error:
Event-driven DI module test in
subunit A:
-
DI module defective
-
CH DQ module defective
-
Wiring error
Byte No. of the DI module which
could contain an error,
decimal display
Byte No. of the relevant CH DQ byte
which could contain an error,
decimal display
Decimal display
S5-115F Manual
Remedy
-
Replace module
-
Replace module
-
Check wiring
Warm restart in the case of
individual error in signal group
No. 0 (Stop mode):
1. Stop/Run
Warm restart in the case of
individual error in signal group
No. 1 to 28
(passivation):
a) Test mode:
1. POWER OFF/ON
2. Stop/Run
b) Safety mode:
1. OVERALL RESET
Warm restart in the case of error
burst:
1. POWER OFF/ON
2. Stop/Run
This does not cancel passivation.
To do so, see above: Warm
restart in the case of passivation.
EWA 4NEB 811 6149-02

Advertisement

Table of Contents
loading

This manual is also suitable for:

S5-115f

Table of Contents