Siemens SIMATIC S5 Manual page 288

Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
31
01
Error in other subunit:
Partner or CPU error
Additional info. 1:
Subunit of the original mess.
31
02
Contradictory error message:
CPU error
Additional info. 1:
Contents of error DB byte in A
Additional info. 2:
Contents of error DB byte in B
Additional info. 3:
Byte No. in error DB incl.
header
31
03
Contradictory error message:
CPU error
Additional info. 1:
Signal group No.
31
04
Contradictory error message:
CPU error
B-28
Possible Cause
Error group No. 23
Subunit which discovered the error
Error group No. 29
Error messages in A and B are
different
Error group No. 29
Signal group No. in error message
does not match (not ident. 0 to 28)
Error group No. 29
Error identifier byte does not match;
Error cannot be evaluated
S5-115F Manual
Remedy
-
Analyze error message in
partner PLC
Warm restart:
1. POWER OFF/ON
2. Stop/Run
Warm restart:
1. POWER OFF/ON
2. Stop/Run
If error not corrected after
repeated POWER OFF/ON:
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
If error not corrected after
repeated POWER OFF/ON:
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
If error not corrected after
repeated POWER OFF/ON:
-
Service
EWA 4NEB 811 6149-02

Advertisement

Table of Contents
loading

This manual is also suitable for:

S5-115f

Table of Contents