PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
108
01
Non-defined interrupt:
CPU HW or handling error
108
02
Power failure in central rack
108
03
Configured scan time
exceeded
Additional info. 1:
Configured scan time/
10 msec.
Additional info. 2:
Actual scan time/10 msec.
108
04
Stack overflow during
interrupt processing:
Handling error
Additional info. 1:
Current stack pointer
Additional info. 2:
Maximum stack pointer
B-66
Possible Cause
Error group No. 1
Interrupt >< ZYK, NAU, INTERRUPT
INTA-N
-
CPU HW error
-
Non-defined interrupt in CPU
Error group No. 18
Error group No. 21
-
Endless loop in user program
-
Configured scan time too short
Setpoint scan time, decimal display
Actual scan time, decimal display
Error group No. 16
-
Interrupt signal frequency too
high
S5-115F Manual
Remedy
-
Replace CPU
-
Impermissible module
connected (intelligent I/Os)
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Check power supply
Warm restart:
1. Stop/Run
-
Remove program errors
-
Increase configured scan time
( Vol. 1, 10.4 of the Manual)
CAUTION:
Value requires authorization
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Check interrupt signal sensor
Warm restart:
1. POWER OFF/ON
2. Stop/Run
EWA 4NEB 811 6149-02