Siemens SIMATIC S5 Manual page 284

Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
30
04
Self-test in A and B not
synchronous: CPU error
Additional info. 1:
FXTE ZEI1 H in A
Additional info. 2:
FXTE ZEI1 H in B
30
05
Self-test in A and B not
synchronous: CPU error
Additional info. 1:
FXTE ZEI1 L in A
Additional info. 2:
FXTE ZEI1 L in B
30
06
Self-test in A and B not
synchronous: CPU error
Additional info. 1:
FXTE ZEI2 H in A
Additional info. 2:
FXTE ZEI2 H in B
B-24
Possible Cause
Error group No. 13
Test pointer 0 (FXTE ZEI0 H) is not
identical in A and B.
-
CPU error (one-sided overwrite
of memory location)
Error group No. 13
Test pointer 1 (FXTE ZEI1 L) is not
identical in A and B.
-
CPU error (one-sided overwrite
of memory location)
Error group No. 13
Test pointer 2 (FXTE ZEI2 H) is not
identical in A and B.
-
CPU error (one-sided overwrite
of memory location)
S5-115F Manual
Remedy
-
Replace CPU
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Replace CPU
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Replace CPU
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
EWA 4NEB 811 6149-02

Advertisement

Table of Contents
loading

This manual is also suitable for:

S5-115f

Table of Contents