PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
253
01
FB253 call with wrong
parameter:
Programming error
253
02
FB253 call with wrong source
slave No., high byte:
Programming error
Additional info. 1:
Source slave No.
253
03
FB253 call with wrong source
slave No., low byte:
Programming error
Additional info. 1:
Source slave No.
253
04
FB253 call with non-configu-
red source slave No.:
Programming or
configuration error
Additional info. 1:
Source slave No.
B-84
Possible Cause
Error group No. 12
-
Wrong parameter format
Error group No. 12
-
Wrong slave No. in high byte;
correct value = 0
Number of the wrong source slave,
decimal display
Error group No. 12
-
Wrong slave No. in low byte;
correct value:
Slave No. > 0 and < 31
Number of the wrong source slave,
decimal display
Error group No. 12
-
Wrong slave No. programmed
-
Source slave No. specified not
configured
Number of source slave not found,
decimal display
S5-115F Manual
Remedy
-
Correct actual parameter
Warm restart:
1. Stop/Run
-
Correct actual parameter
Warm restart:
1. Stop/Run
-
Correct actual parameter
Warm restart:
1. Stop/Run
-
Correct actual parameter
-
Correct configuration
Warm restart:
1. Stop/Run
EWA 4NEB 811 6149-02