PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
252
06
Wrong character entered for
memory type:
Programming error
Additional info 1:
Wrong character
252
07
Number of blocks <1 or
>32:
Programming error
252
08
Data block missing:
Handling error
Additional info 1:
DB number
252
09
Too few data words
provided:
Handling error
252
10
Too few flag words provided:
Handling error
B-82
Possible Cause
Error group No. 12
Error group No. 12
-
Illegal block length specified
Error group No. 12
-
DB missing
DB number entered
Decimal display
Error group No. 12
-
Insufficient memory space
Error group No. 12
-
Insufficient memory space
S5-115F Manual
Remedy
-
Check FB 252 parameters
Warm restart:
1. Stop/Run
-
Check FB 252 parameters
Warm restart:
1. Stop/Run
-
Provide more memory space
Warm restart:
1. Stop/Run
-
Provide more memory space
Warm restart:
1. Stop/Run
-
Provide more memory space
Warm restart:
1. Stop/Run
EWA 4NEB 811 6149-02