Siemens SIMATIC S5 Manual page 329

Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

S5-115F Manual
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
109
06
Illegal access on I/O area with
LIR, TIR order:
Programming error
Additional info. 1:
DQ byte/word No.
109
07
TPB/TPW operation on
unconnected DQ module:
Programming error
Additional info. 1:
DQ byte/word No.
109
08
Illegal TNB operation on I/O
area:
Programming error
Additional info. 1:
Current source address
Additional info. 2:
Current destination address
Additional info. 3:
Current residual length
EWA 4NEB 811 6149-02
Possible Cause
Error group No. 12
-
The addresses given in LIR and TIR
belong to an illegal area,
< 4 Kbytes,> 60 Kbytes or TIR
addr. > 49 Kbytes (operating
system data)
Source or destination address used,
hex dispaly
Error group No. 12
-
Wrong address given for T PY or
T BW operation
or address not
* configured
* connected
Word address of unconnected
module, decimal display
Error group No. 12
Illegal range, < 4 Kbytes,
>60 Kbytes
Source or destination address used,
hex display
At the beginning of execution, the
residual length is equal to the
parameter.
PLC Error Messages
Remedy
-
Remove programming errors
Warm restart:
1. Stop/Run
-
Change address
*
Configure address
*
Connect and configure
module
Warm restart:
1. Stop/Run
-
Remove programming error
(change address)
Warm restart:
1. Stop/Run
B-69