PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
106
01
PG operator DB too long
(>4068 bytes):
Handling error
Additional info. 1:
DB No.
Additional info. 2:
DB length
106
02
DB does not belong in user
RAM: Handling error
Additional info. 1:
DB No.
Additional info. 2:
DB length
B-64
Possible Cause
Error group No. 16
No. of the PG operator DB,
decimal display
Length of PG operator DB in byte,
hex display
Error group No. 16
-
RAM requirement of user system
greater than available RAM
No. of the PG operator DB,
decimal display
S5-115F Manual
Remedy
-
Shorten PG operator DB
(<= 4068 bytes)
Warm restart:
1. Stop/Run
-
Reduce RAM requirement of
user system
-
Enlarge RAM in test
operation: max. size of RAM
submodule equal to user
EPROM in safety mode
-
Reduce RAM requirement of
user system in safety mode
Warm restart:
1. Stop/Run