Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
102
01
User memory submodule for
S5-115F not permissible:
Handling error
Additional info. 1:
Submodule identifier
102
02
Different user memory
submodule types in A and B:
Handling error
Additional info. 1:
Submodule identifier of A
Additional info. 2:
Submodule identifier of B
102
03
Different user programs in A
and B:
Handling error
Additional info. 1:
Signature of A
Additional info. 2:
Signature of B
102
04
Backup battery is empty or
missing
EWA 4NEB 811 6149-02
Possible Cause
Error group No. 30
-
Wrong user memory submodule
plugged in
Submodule identifier of the
submodule used; hex display
Error group No. 24
Submodule ID of EPROM in
subunit A
Submodule ID of EPROM in
subunit B;
Hex display
Error group No. 24
Different user program signatures in
the subunits:
-
Different user program versions
-
EPROM defective
Error group No. 25
PLC Error Messages
Remedy
-
Use permissible user memory
submodule
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Use the same user memory
submodule type for both
subunits
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Use COM 115F to write the
same user program (same
signature) in EPROM
-
Replace EPROM
Warm restart:
1. POWER OFF/ON
2. Stop/Run
Replace battery
Warm restart:
1. Stop/Run
B-57