Introduction to STEP 5
Table 2-4. Block Parameter Types and Data Types with Permissible Actual Operands
Parameter
Data Type
Type
I, Q
BI
BY
W
D
KM
KY
KH
KS
KT
KC
KF
B
Type designation not permitted
T
Type designation not permitted
C
Type designation not permitted
2-16
for an operand with bit address
for an operand with byte address
for an operand with word address
for a binary pattern (16 digits)
for two absolute numbers, one byte
each, each in the range from 0 to 255
for a hexadecimal pattern (maximum
4 digits)
for a character (maximum 2
alphanumeric characters)
for a time (BCD-coded time) with time
base 1.0 to 999.3
for a count (BCD-coded) 0 to 999
for a fixed-point number in the range
from -32768 to +32767
Permissible Actual Operands
I
x.y inputs
Q
x.y outputs
F
x.y flags
IB
x
input bytes
QB x
output bytes
FB x
flag bytes
DL x
data bytes left
DR x
data bytes right
PB x
peripheral bytes
IW x
input words
QW x
output words
FW x
flag words
DW x
data words
PW x
peripheral words
Constants
DB x
Data blocks. The C DBx operation is
executed.
FB x
Function blocks (permissible without
parameters only) are called
unconditionally (JU..x).
PB x
Program blocks are called
unconditionally (JU..x).
SB x
Sequence blocks are called
unconditionally (JU..x).
T
Timer. The time should be assigned
parameters as data or be
programmed as a constant in the
function block.
Z
Counter. The count should be
assigned parameters as data or be
programmed as a constant in the
function block.
EWA 4NEB 811 6149-02
S5-115F Manual