Power Supplies; Individual Module Parameters; Interface/Relay Cards - Honeywell 5701 Operating Instructions Manual

Sieger system 57
Table of Contents

Advertisement

MAN0443.P65 Issue 13 Aug 04
05701-M-5001 A02279
CHAPTER 8 - SPECIFICATION
LV Directive 73/23/EEC
Constructed in accordance with good engineering practice. Guided by
the principles of EN 61010/1 1990/1992.
4.

POWER SUPPLIES

Power Consumption :
(System)
External DC Power Supply: 18V to 32V to DC Input Card.
External AC Power Supply: 85V to 264V at 47Hz to 440Hz.
5.

INDIVIDUAL MODULE PARAMETERS

5.1

Interface/Relay Cards

Dimensions:
Weight:
Power:
Relay Operation:
Relay Contact Rating:
Field Terminals:
Dependent upon configuration.
See Chapter 4, Section 5.
(Using optional AC to DC PSU).
Height 112mm.
Width 25mm.
Depth 102mm.
Field Interface
Double SPCO
Triple SPCO
Triple DPCO
High Integrity
Field Interface
Double SPCO
Triple SPCO
Triple DPCO
High Integrity
Selectable.
Latching/Non-Latching.
Energised/De-Energised.
5A at 110V/250V ac (non inductive).
5A at 32V dc (non- inductive).
2
2.5mm
(14 AWG).
8 - 4
5701 Control System
95g.
155g.
205g.
245g.
255g.
0.0W.
0.8W.
1.0W.
1.6W.
1.7W.

Hide quick links: