10.5 Timer, Counter, High-Speed Counter, High-Speed Output, Clock,

and Pulse Instructions

On-Delay Timer, Retentive On-Delay Timer
L
Txxx
A
D
IN
PT
Txxx
IN
PT
S
TON
T
L
TONR
212
214
TON and TONR timers are available in three resolutions. The resolution is determined by the
timer number and is shown in Table 10-3. Each count of the current value is a multiple of the
time base. For example, a count of 50 on a 10-millisecond (ms) timer represents 500 ms.
Table 10-3
Timer
Resolution
TON
1 ms
10 ms
100 ms
TONR
1 ms
10 ms
100 ms
S7-200 Programmable Controller System Manual
C79000-G7076-C230-02
The On-Delay Timer and Retentive On-Delay Timer
instructions time up to the maximum value when enabled. When
the current value (Txxx) is >= to the Preset Time (PT), the timer
TON
bit turns on.
The On-Delay timer is reset when disabled, while the Retentive
On-Delay timer stops timing when disabled. Both timers stop
timing when they reach the maximum value.
TONR
Operands:
Txxx, PT
Txxx, PT
215
216
Timer Numbers and Resolutions
Maximum Value
32.767 seconds (s) T32
327.67 s
T33 to T36
3276.7 s
T37 to T63
32.767 s
T0
327.67 s
T1 to T4
3276.7 s
T5 to T31
Txxx:
TON
TONR
1 ms
T32, T96
T0, T64
10 ms
T33 to T36
T1 to T4
T97 to T100
T65 to T68
100 ms
T37 to T63
T5 to T31
T101 to T255
T69 to T95
PT:
VW, T, C, IW, QW, MW, SMW, AC,
AIW, Constant, *VD, *AC, SW
CPU 212
CPU 214
T32, T96
T33 to T36,
T97 to T100
T37 to T63,
T101 to T127
T0, T64
T1 to T4,
T65 to T68
T5 to T31,
T69 to T95
Instruction Set
CPU 215/216
T32, T96
T33 to T36,
T97 to T100
T37 to T63,
T101 to T255
T0, T64
T1 to T4,
T65 to T68
T5 to T31,
T69 to T95
10-13