Cpu 212 Ac Power Supply, Dc Inputs, Relay Outputs - Siemens Simatic S7-200 System Manual

Programmable controller
Hide thumbs Also See for Simatic S7-200:
Table of Contents

Advertisement

S7-200 Data Sheets
A.3

CPU 212 AC Power Supply, DC Inputs, Relay Outputs

Order Number: 6ES7 212-1BA01-0XB0
General Features
Physical size (L x W x D)
160 x 80 x 62 mm
(6.3 x 3.15 x 2.44 in.)
Weight
0.4 kg (0.9 lbs.)
Power dissipation
6 W
User program size/storage
512 words/EEPROM
User data size/storage
512 words/RAM
Data retention
50 hr typical
(8 hr minimum at 40 C)
1
Local I/O
8 inputs/6 outputs
Maximum number of
2
expansion modules
Digital I/O supported
64 inputs/64 outputs
Analog I/O supported
16 inputs/16 outputs
1.2 µs/instruction
Boolean execution speed
Internal memory bits
128
Timers
64 timers
Counters
64 counters
High-speed counters
1 software (2 KHz max.)
Analog adjustments
1
Standards compliance
UL 508
FM Class I, Division 2
VDE 0160 compliant
CE compliant
Output Points
Output type
Relay, dry contact
Voltage range
5 to 30 VDC/250 VAC
Maximum load current
2 A/point, 6 A/common
Overcurrent surge
7 A with contacts closed
Isolation resistance
100 M minimum (new)
Switching delay
10 ms maximum
Lifetime
10,000,000 mechanical
100,000 with rated load
Contact resistance
200 m maximum (new)
Isolation
coil to contact
1500 VAC, 1 min
contact to contact
750 VAC, 1 min
(between open contacts)
Short circuit protection
None
1
The CPU reserves 8 process-image input and 8 process-image output image register points for local I/O.
A-8
Input Points
Input type (IEC 1131-2)
ON state range
ON state nominal
OFF state maximum
Response time
I0.0 to I0.7
Optical isolation
Power Supply
Voltage/frequency range
Input current
Holdup time
Inrush current
Fusing (non-replaceable)
5 VDC current
Isolated
CSA C22.2 142
DC Sensor Supply
Voltage range
Ripple/noise (<10MHz)
24 VDC available current
Short circuit current limit
Isolated
S7-200 Programmable Controller System Manual
Type 1 sinking
15-30 VDC, 4 mA minimum
35 VDC, 500 ms surge
24 VDC, 7 mA
5 VDC, 1 mA
0.3 ms maximum
500 VAC, 1 min
85 to 264 VAC at 47 to 63 Hz
4 VA typical, CPU only
50 VA maximum load
20 ms minimum from
110 VAC
20 A peak at 264 VAC
2 A, 250 V, slow blow
260 mA for CPU
340 mA for expansion I/O
Yes. Transformer, 1500 VAC,
1 min
20.4 to 28.8 VDC
1 V peak-to-peak maximum
180 mA
< 600 mA
No