Configuring
9.9 Configuration of digital inputs/outputs (X142)
Measurement method
Depending on the selected measurement method, the period duration is determined based
on the "last period" or "all periods" in a measuring cycle.
Note
"Multiple periods" measurement method when using unsupported hardware
If a SIMATIC Drive Controller does not meet the hardware function version (FS 11 or higher)
requirement, the CPU remains in startup inhibit state.
Additional information
You can find more information on the Event/period duration measurement operating mode in
Assignment of the control interface (Page 191) and Assignment of the feedback interface
(Page 192).
9.9.8

Configuring Pulse width modulation (PWM) operating mode

Areas of application
You can use pulse width modulation (PWM) to generate periodic pulses with a constant rated
voltage and a variable pulse duration.
Possible applications for pulse width modulation (PWM):
• Control of proportional valves and directional valves
– Energy savings as a result of a reduction in holding current or for controlling the valve
• Heating control, for example, via an external additional power unit
Principle of operation
With pulse width modulation, a signal with defined time period and variable pulse duration is
output at the digital output. You use pulse width modulation to vary the mean value of the
output voltage. This allows you to control the load current or the power in line with the
connected load. The pulse duration can be between 0 (no pulse, always off) and full-scale
deflection (no pulse, always on).