CPU 212 AC Power Supply, AC Inputs, Relay Outputs

Order Number: 6ES7 212-1GA01-0XB0
General Features
Physical Size (L x W x D)
160 x 80 x 62 mm
(6.3 x 3.15 x 2.44 in.)
Weight
0.4 kg (0.9 lbs.)
Power Dissipation
6 W
User program size/storage
512 Words / EEPROM
User data size/storage
512 Words / RAM
Data retention
50 hr typical
(8 hr minimum at 40 C)
1
Local I/O
8 Inputs / 6 Outputs
Maximum Number of
2
Expansion Modules
Digital I/O Supported
64 Inputs / 64 Outputs
Analog I/O Supported
16 Inputs / 16 Outputs
1.2 µs/instruction
Boolean Execution Speed
Internal Memory Bits
128
Timers
64 Timers
Counters
64 Counters
High-speed counters
1 Software (2 KHz max.)
Analog Adjustments
1
Standards Compliance
UL 508
FM Class I, Division 2
VDE 0160 compliant
CE compliant
Output Points
Output Type
Relay, dry contact
Voltage Range
5 to 30 VDC / 250 VAC
Maximum Load Current
2 A/point
Overcurrent Surge
7 A with contacts closed
Isolation Resistance
100 M minimum (new)
Switching Delay
10 ms maximum
Lifetime
10,000,000 Mechanical
100,000 with Rated Load
Contact Resistance
200 m maximum (new)
Isolation
Coil to Contact
1500 VAC, 1 minute
Contact to Contact
1000 VAC, 1 minute
Short Circuit Protection
None
1
The CPU reserves 8 input and 8 output image register points for local I/O.
A-18
Input Points
Input Type (IEC 1131-2)
ON State Range
ON State Nominal
OFF State Maximum
Response Time
Optical Isolation
Power Supply
Voltage/frequency Range
Input Current
Hold Up Time
Inrush Current
Fusing (non-replaceable)
5 VDC Current
Isolated
DC Sensor Supply
CSA C22.2 142
Voltage Range
Ripple/noise (<10Mhz)
24 VDC Available Current
Short Circuit Current Limit
Isolated
S7-200 Programmable Controller System Manual
Type 1 Sinking
79 to 135 VAC, 47 to 63 Hz.
4 mA minimum
120 VAC, 60 Hz, 7mA
20 VAC, 1 mA
10 ms typical, 15 ms max.
1500 VAC, 1 minute
85 to 264 VAC at 47 to 63 Hz
4 VA typical, CPU only
50 VA maximum load
20 ms minimum from
110 VAC
20 A peak at 264 VAC
2 A, 250 V, Slow Blow
260 mA for CPU
340 mA for expansion I/O
Yes. Transformer, 1500 VAC,
1 minute
20.4 to 28.8 VDC
1 V peak-to-peak maximum
180 mA
< 600 mA
No
C79000-G7076-C230-02