Cpu 214 Ac Power Supply, Ac Inputs, Ac Outputs - Siemens Simatic S7-200 System Manual

Programmable controller
Hide thumbs Also See for Simatic S7-200:
Table of Contents

Advertisement

S7-200 Data Sheets
A.11 CPU 214 AC Power Supply, AC Inputs, AC Outputs
Order Number: 6ES7 214-1CC01-0XB0
General Features
Physical size (L x W x D)
197 x 80 x 62 mm
(7.76 x 3.15 x 2.44 in.)
Weight
0.5 kg (1.0 lbs.)
Power dissipation
11 W at 4.25 A load
User program size/storage
2 Kwords/EEPROM
User data size/storage
2 Kwords/RAM
Data and TOD retention
Supercap
190 hr typ. (120 hr minimum
Optional battery
200 days continuous usage
1
Local I/O
14 inputs/10 outputs
Max. I/O expansion modules
7
Digital I/O supported
64 inputs/64 outputs
Analog I/O supported
16 inputs/16 outputs
0.8 µs/instruction
Boolean execution speed
Internal memory bits
256
Timers
128 timers
Counters
128 counters
High-speed counters
1 software (50 Hz)
2 hardware (50 Hz each)
TOD Clock tolerance
6 minutes per month
Pulse outputs
2 (100 Hz each)
Analog adjustments
2
Standards compliance
UL 508
FM Class I, Division 2
CE compliant
Input Points
Input type (IEC 1131-2)
Type 1 sinking
ON state range
79 to 135 VAC, 47 to 63 Hz,
4 mA minimum
ON state nominal
120 VAC, 60 Hz, 7 mA
OFF state maximum
20 VAC, 1 mA
Maximum response time
0.2 ms to 8.7 ms selectable
plus 15.0 ms for fixed filter
15.2 ms default
Optical isolation
1500 VAC, 1 min
1
The CPU reserves 16 process-image input and 16 process-image output register points for local I/O.
2
Linear derate 40 to 55 C. Vertical mount derate 10 C
A-24
Output Points
Output type
Voltage/frequency range
Load circuit power factor
Inductive load clamping
Maximum Load Current
per single point
per 2 adjacent points
all points total
Minimum load current
at 40 C)
Leakage current
Switching delay
Surge current
Voltage drop
Optical isolation
Short circuit protection
Power Supply
Voltage / Frequency Range
Input Current
Hold Up Time
Inrush Current
Fusing (non-replaceable)
CSA C22.2 142
5 VDC Current
Isolated
DC Sensor Supply
Voltage Range
Ripple/noise (<10MHz)
24 VDC Available Current
Short Circuit Current Limit
Isolated
Triac, zero-crossing
20 to 264 VAC, 47 to 63 Hz
0.3 to 1.0
MOV 275 V working voltage
0 to 40 C
1.20 A
1.50 A
6.00 A
30 mA
1.5 mA, 120 VAC/2.0 mA,
240 VAC
1/2 cycle
30 A peak, 1 cycle /
10 A peak, 5 cycle
1.5 V maximum at maximum
current
1500 VAC, 1 min
None
85 to 264 VAC at 47 to 63 Hz
4.5 VA typical, CPU only
50 VA maximum load
20 ms min. from 110 VAC
20 A peak at 264 VAC
2 A, 250 V, slow blow
440 mA for CPU
560 mA for expansion I/O
Yes. Transformer, 1500 VAC,
1 min
20.4 to 28.8 VDC
<1 V peak-to-peak maximum
280 mA
< 600 mA
No
S7-200 Programmable Controller System Manual
C79000-G7076-C230-02
2
55 C
1.00 A
1.25 A
4.25 A

Advertisement

Table of Contents
loading