Siemens Simatic S7-200 System Manual page 329

Programmable controller
Hide thumbs Also See for Simatic S7-200:
Table of Contents

Advertisement

Table A-1
Technical Specifications for the S7-200 Family, continued
Electromagnetic Compatibility — Conducted and Radiated Emissions
EN 55011, Class A, Group 1, conducted
0.15 MHz to 0.5 MHz
0.5 MHz to 5 MHz
5 MHz to 30 MHz
EN 55011, Class A, Group 1, radiated
30 MHz to 230 kHz
230 MHz to 1 GHz
EN 55011, Class B, Group 1, conducted
0.15 to 0.5 MHz
0.5 MHz to 5 MHz
5 MHz to 30 MHz
EN 55011, Class B, Group 1, radiated
30 MHz to 230 kHz
230 MHz to 1 GHz
High Potential Isolation Test
24 V/5 V nominal circuits
115/230 V circuits to ground
115/230 V circuits to 115/230 V circuits
230 V circuits to 24 V/5 V circuits
115 V circuits to 24 V/5 V circuits
1
Unit must be mounted on a grounded metallic frame with the S7-200 ground connection made directly to the mounting metal. Cables
are routed along metallic supports.
2
Applicable for all devices bearing the CE (European Community) mark.
3
Unit must be mounted in a grounded metal enclosure. AC input power line must be equipped with a Schaffner FN 680-2.5/06 filter
or equivalent, 25. cm max. wire length from filters to the S7-200. The 24 VDC supply and sensor supply wiring must be shielded.
Relay Electrical Service Life
Figure A-1 shows typical performance data supplied by relay vendors. Actual performance
may vary depending upon your specific application.
Figure A-1
S7-200 Programmable Controller System Manual
C79000-G7076-C230-02
1
< 79 dB (µV) Quasi-peak; < 66 dB (µV) Average
< 73 dB (µV) Quasi-peak; < 60 dB (µV) Average
< 73 dB (µV) Quasi-peak; < 60 dB (µV) Average
1
30 dB (µV/m) Quasi-peak; measured at 30 m
37 dB (µV/m) Quasi-peak; measured at 30 m
3
< 66 dB (µV) Quasi-peak decreasing with log frequency to 56 dB (µV);
< 56 dB (µV) Average decreasing with log frequency to 46 dB (µV)
< 56 dB (µV) Quasi-peak; < 46 dB (µV) Average
< 60 dB (µV) Quasi-peak; < 50 dB (µV) Average
3
30 dB (µV/m) Quasi-peak; measured at 10 m
37 dB (µV/m) Quasi-peak; measured at 10 m
500 VAC (optical isolation boundaries)
1,500 VAC
1,500 VAC
1,500 VAC
1,500 VAC
4000
1000
500
300
100
250 VAC inductive load (p.f.=0.4)
30 VDC inductive load (L/R=7msec)
0
1
2
Rated Operating Current (A)
Electrical Service Life
S7-200 Data Sheets
2
per EN50081 -1 and -2
250 VAC resistive load
30 VDC resistive load
3
4
5
6
7
2
A-5