Installation And Operating Instructions; Shaft Installation - Siemens SQM50.261R1Z3 Technical Instructions

Reversing
Hide thumbs Also See for SQM50.261R1Z3:
Table of Contents

Advertisement

SQM5... Reversing Actuators
Installation and
Operation
Instructions

Shaft Installation

Siemens Building Technologies, Inc.
SQM5... actuators are sometimes shipped without the shaft installed. To install the
selected shaft:
1. Loosen the two screws on the actuator cover corners. See Figure 2.
2. Lift the screws and raise the cover. See Figure 3.
Figure 2.
3. Each shaft is supplied with two washers and a "C" clip. See Figure 4. Using
spreading pliers, remove the "C" clip and the washers from the shaft.
4. Insert the "insert end" of the shaft into the "gear end" of the actuator.
5. Push the shaft until the "insert end" reaches just short of the brass bushing at the
other end of the actuator.
6. Put one of the washers on the insert end of the shaft. See Figure 5.
7. Line up the "shaft key" with the key slot on the "gear end" of the actuator and slide
the shaft until the "insert end" is completely through the brass bushing.
8. Place the second washer onto the "insert end" of the shaft. Using spreading pliers,
install the "C" clip.
Figure 3.
Figure 4.
Figure 5.
Technical Instructions
Document No. 155-517P25
Mar 3, 2021
Page 7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents