The divergence of control streams can be implemented in an SCR program by using multiple
SCRT instructions enabled by the same transition condition, as shown in Figure 10-41.
Network
Network
. . .
Network
M2.3
Network
Figure 10-41
S7-200 Programmable Controller System Manual
C79000-G7076-C230-02
LAD
S3.4
Beginning of State L
SCR
control region
I2.1
S3.5
Transition to State M
SCRT
S6.5
Transition to State N
SCRT
End of SCR region for
SCRE
State L
Example of Divergence of Control Streams
Instruction Set
STL
Network
LSCR
S3.4
Network
. . .
Network
LD
M2.3
A
I2.1
SCRT
S3.5
SCRT
S6.5
Network
SCRE
10-95