Siemens Simatic S7-200 System Manual page 328

Programmable controller
Hide thumbs Also See for Simatic S7-200:
Table of Contents

Advertisement

S7-200 Data Sheets
Technical Specifications
The S7-200 CPUs and all S7-200 expansion modules conform to the technical specifications
listed in Table A-1.
Table A-1
Technical Specifications for the S7-200 Family
Environmental Conditions — Transport and Storage
IEC 68-2-2, Test Bb, Dry heat and
IEC 68-2-1, Test Ab, Cold
IEC 68-2-30, Test Db, Damp heat
IEC 68-2-31, Toppling
IEC 68-2-32, Free fall
Environmental Conditions — Operating
Functional range
IEC 68-2-14, Test Nb
IEC 68-2-27 Mechanical shock
IEC 68-2-6 Sinusoidal vibration
EN 60529, IP20 Mechanical protection
Electromagnetic Compatibility — Immunity
EN 61000-4-2 (IEC 801-2)
Electrostatic discharge
EN 50140 (IEC 801-3)
Radiated electromagnetic field
EN50204
EN 61000-4-4 (IEC 801-4)
Fast transient bursts
EN 61000-4-5 (IEC 801-5)
Surge immunity
VDE 0160 Non-periodic overvoltage
A-4
-40 C to +70 C
25 C to 55 C, 95% humidity
100 mm, 4 drops, unpacked
1 m, 5 times, packed for shipment
0 C to 55 C, 95% maximum non-condensing humidity
5 C to 55 C, 3 C/minute
15 G, 11 ms pulse, 6 shocks in each of 3 axis
0.35 mm peak-to-peak 10 to 57 Hz; 2 G panel mount, 1G DIN rail
mount, 57 Hz to 150 Hz; 10 sweeps each axis, 1 octave/minute
Protects against finger contact with high voltage as tested by standard
probes. External protection is required for dust, dirt, water, and foreign
objects of less than 12.5 mm in diameter.
1
1
per EN50082-2
8 kV air discharge to all surfaces and communication port
26 MHz to 1 GHz 10 V/m, 80% modulation with 1 kHz signal
900 MHz
5 MHz, 10 V/m, 50% duty cycle, 200 Hz repetition
frequency
2 kV, 5 kHz with coupling network to AC and DC system power
2 kV, 5 kHz with coupling clamp to digital I/O and communications
2 kV asymmetrical, 1 kV symmetrical
5 positive/5 negative pulses 0 , +90 , -90 phase angle
(24 VDC circuits require external surge protection)
at 85 VAC line, 90 phase angle, apply 390 V peak, 1.3 ms pulse
at 180 VAC line, 90 phase angle, apply 750 V peak, 1.3 ms pulse
S7-200 Programmable Controller System Manual