Table A-5
Specifications for DC and AC Powered S7-200 CPUs
Full Scale Input
Range
Range
% of Full Scale
Specifications for DC Powered S7-200 CPUs
0 to 50 mV
0 to 100 mV
0 to 500 mV
0 to 1 V
0.075%
0 075%
0 to 5 V
0 to 20 mA
0 to 10 V
25 mV
50 mV
100 mV
250 mV
500 mV
0.075%
1 V
2.5 V
5 V
10 V
Specifications for AC Powered S7-200 CPUs
0 to 50 mV
0 to 100 mV
0 to 500 mV
0 to 1 V
0.15%
0 15%
0 to 5 V
0 to 20 mA
0 to 10 V
25 mV
50 mV
100 mV
250 mV
500 mV
0.15%
1 V
2.5 V
5 V
10 V
1
Measurements made after the selected input range has been calibrated.
2
The offset error in the signal near zero analog input is not corrected, and is not included in the accuracy specifications.
3
There is a channel-to-channel carryover conversion error, due to the finite settling time of the analog multiplexer. The
maximum carryover error is 0.1% of the difference between channels.
4
Mean accuracy includes effects of non-linearity and drift from 0 to 55 degrees C.
S7-200 Programmable Controller System Manual
C79000-G7076-C230-02
1
Repeatability
Counts
24
24
48
48
48
96
S7-200 Data Sheets
1, 2, 3, 4
Mean (average) Accuracy
% of Full Scale
Counts
0.25%
80
0.2%
64
0.05%
0.05%
16
16
0.25%
160
0.2%
128
0.1%
64
0.05%
0.05%
32
32
0.25%
80
0.2%
64
0.05%
0.05%
16
16
0.25%
160
0.2%
128
0.1%
64
0.05%
0.05%
32
32
A-77