Recommended Power Cable Types; Power Cable Types For Limited Use; Not Allowed Power Cable Types - ABB ACS380 Hardware Manual

Hide thumbs Also See for ACS380:
Table of Contents

Advertisement

Recommended power cable types

PE
PE
PE

Power cable types for limited use

PE
PVC
EMT

Not allowed power cable types

PE
Symmetrical shielded cable with three phase conductors and a
concentric PE conductor as shield. The shield must meet the
requirements of IEC 61800-5-1, refer to page 48. Check with local / state
/ country electrical codes for allowance.
Symmetrical shielded cable with three phase conductors and a
concentric PE conductor as the shield. A separate PE conductor is
required if the shield does not meet the requirements of IEC 61800-5-1,
refer to page 48.
Symmetrical shielded cable with three phase conductors and
symmetrically constructed PE conductor, and a shield. The PE conductor
must meet the requirements of IEC 61800-5-1, refer to page 48.
A four-conductor system (three phase conductors and a protective
conductor on a cable tray) is not permitted for motor cabling (it is
permitted for input cabling).
A four-conductor system (three phase conductors and a PE conductor in
a PVC conduit) is permitted for input cabling with a phase conductor
cross-section less than 10 mm
(40 hp). Not permitted in the USA.
Corrugated or EMT cable with three phase conductors and a protective
conductor is permitted for motor cabling with a phase conductor cross
section less than 10 mm
Symmetrical shielded cable with individual shields for each phase
conductor is not permitted in any cable size for input or motor cabling.
Planning the electrical installation 51
2
(8 AWG) or for motors < 30 kW
2
(8 AWG) or for motors < 30 kW (40 hp).