Fuses (Iec); Gg Fuses - ABB ACS380 Hardware Manual

Hide thumbs Also See for ACS380:
Table of Contents

Advertisement

Fuses (IEC)

The table lists gG, UL, and uR or aR fuses for protection against short-circuit in the
input power cable or drive. Either fuse type can be used if it operates rapidly enough.
The operating time depends on the supply network impedance, and the cross-
sectional area and length of the supply cable. Refer to
protection
on page 56.
Do not use fuses with a higher current rating than given in the table.
You can use fuses from other manufacturers, if they meet the ratings, and if the
melting curve of the fuse does not exceed the melting curve of the fuse mentioned in
the table.

gG fuses

Make sure that the operating time of the fuse is less than 0.5 seconds. Obey the local
regulations.
Type
Input
current
ACS380-04xx
A
1-phase U
= 200...240 V
N
02A4-1
5.0
03A7-1
7.8
04A8-1
10.1
06A9-1
14.5
07A8-1
16.4
09A8-1
20.6
12A2-1
25.6
3-phase U
= 200...240 V
N
02A4-2
3.8
03A7-2
5.9
04A8-2
7.7
06A9-2
11.0
07A8-2
12.5
09A8-2
15.7
12A2-2
19.5
17A5-2
28.0
25A0-2
40.0
032A-2
51.2
048A-2
76.8
055A-2
88.0
Min. short-
Nominal
circuit
current
current
A
A
80
10
80
10
128
16
200
20
200
25
256
32
320
35
48
6
80
10
80
10
128
16
128
16
128
16
200
25
256
32
400
50
504
63
800
100
800
100
Implementing short-circuit
2
I
t
Voltage
rating
2
A
s
V
380
500
380
500
720
500
1500
500
2500
500
2500
500
7000
500
110
500
360
500
360
500
740
500
740
500
740
500
2500
500
4500
500
15500
500
20000
500
65000
500
65000
500
Technical data 93
ABB type
IEC 60269
size
OFAF000H10
000
OFAF000H10
000
OFAF000H16
000
OFAF000H20
000
OFAF000H25
000
OFAF000H32
000
OFAF000H35
000
OFAF000H6
000
OFAF000H10
000
OFAF000H10
000
OFAF000H16
000
OFAF000H16
000
OFAF000H16
000
OFAF000H25
000
OFAF000H32
000
OFAF000H50
000
OFAF000H63
000
OFAF000H100
000
OFAF000H100
000

Hide quick links: