Free space requirements

Frame size
mm
R0-R4
75
1) You can install the modules side by side, but if you plan to install side-mounted options, leave 20 mm of
space to the right side of the module.

Losses, cooling data and noise

Frame size R0 has natural convection cooling. Frame sizes R1...R4 have a cooling
fan. The air flow direction is from bottom to top.
The table below specifies the heat dissipation in the main circuit at nominal load and
in the control circuit with minimum load (I/O and panel not in use) and maximum load
(all digital inputs in the on state and the panel, fieldbus and fan in use). The total heat
dissipation is the sum of the heat dissipation in the main and control circuits.
Type
ACS380-
Main
04xx
circuit at
rated I
and I
2N
W
1-phase U
= 200...240 V
N
02A4-1
32
03A7-1
46
04A8-1
59
06A9-1
85
07A8-1
95
09A8-1
115
12A2-1
145
3-phase U
= 200...240 V
N
02A4-2
19
03A7-2
26
04A8-2
35
06A9-2
42
07A8-2
50
09A8-2
68
12A2-2
87
17A5-2
116
25A0-2
160
032A-2
218
048A-2
319
055A-2
435
3-phase U
= 380...480 V
N
01A8-4
26
02A6-4
35
03A3-4
42
Above
in
3
Heat dissipation
Control
Control
circuit
circuit
minimum
maximum
1N
W
7
7
9
9
9
9
9
9
9
9
9
9
9
9
11
11
18
18
18
7
9
9
Free space requirement
Below
mm
in
75
3
Air flow
Main and
control
boards
maximum
W
W
18
51
18
65
20
80
20
105
20
115
20
135
20
165
20
39
20
46
20
55
20
62
20
70
20
88
20
107
22
138
22
182
30
247
30
349
30
465
18
44
20
55
20
62
Technical data 101
On the sides
mm
0
3AXD10000299801.xls
Noise
3
m
/h
dB(A)
-
< 30 dB
-
< 30 dB
57
63 dB
57
63 dB
57
63 dB
63
59 dB
63
59 dB
57
63 dB
57
63 dB
57
63 dB
57
63 dB
57
63 dB
57
63 dB
63
59 dB
128
66 dB
128
66 dB
150
69 dB
150
69 dB
150
69 dB
-
< 30 dB
57
63 dB
57
63 dB
(1
in
0
Frame
size
R0
R0
R1
R1
R1
R2
R2
R1
R1
R1
R1
R1
R1
R2
R3
R3
R4
R4
R4
R0
R1
R1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents