Compliance with EN 61800-3:2004 + A1:2012

Definitions

EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic
equipment to operate without problems within an electromagnetic environment.
Likewise, the equipment must not disturb or interfere with any other product or
system within its locality.
First environment includes establishments connected to a low-voltage network which
supplies buildings used for domestic purposes.
Second environment includes establishments connected to a network not directly
supplying domestic premises.
Drive of category C1: drive of rated voltage less than 1000 V and intended for use in
the first environment.
Drive of category C2: drive of rated voltage less than 1000 V and intended to be
installed and started up only by an authorised professional when used in the first
environment.
Drive of category C3: drive of rated voltage less than 1000 V, intended for use in the
second environment and not intended for use in the first environment.

Category C1

The conducted emission limits are complied with the following provisions:
1. The optional EMC filter is selected according to the ABB documentation and
installed as specified in the EMC filter manual.
2. The motor and control cables are selected as specified in this manual.
3. The drive is installed according to the instructions given in this manual.
4. For the maximum motor cable length with 4 kHz switching frequency, refer to
Motor cable length
In a domestic environment, this product can cause radio-frequency inference, in
which case supplementary mitigation measures may be required.

Category C2

Applicable to ACS380-042x with an internal EMC C2 filter.
The emission limits are complied with the following provisions:
1. The motor and control cables are selected as specified in this manual.
2. The drive is installed according to the instructions given in this manual.
3. For the maximum motor cable length with 4 kHz switching frequency, refer to
Motor cable length
on page 107.
on page 107.